← Back to search
UKRSPETSSERVIS TOV
CHERNIGIV
UnclaimedClaim this profile (free)
Subcontracting experience
3 records from government sources. Past participation is not evidence of current teaming interest.
| Role | Agency | Description | Vehicle | Obligated | Action date | Period |
|---|---|---|---|---|---|---|
| Subcontractor | Agency for International Development | PROCUREMENT AND DELIVERY OF MOBILE BOILER HOUSES TO SPECIFICIED LOCATIONS THROUGHOUT UKRAINE 154-UCEM-1810-1202201 Parent award context Parent award agency: Agency for International Development · Agency for International Development Parent award NAICS: 541990 Parent award description: OVERSEAS CONTRACT View parent award on USAspending | — | $3,564,000 | Sep 25, 2023 | — – — |
| Subcontractor | Agency for International Development | DISTRIBUTION OF BOILER HOUSES BY REGIONS AND CAPACITIES IS SHOWN THE TABLE BELOW: CHERNIHIV & REGION, SUMY & REGION, VINNYTSIA, KRAMATORSK, KROPYVNYT-SKYI, AND ODESA.
1. GENERAL REQUIREMENTS:
EXECUTION: CONTAINER MODULAR TRANSPORTABLE
THE PURPOSE OF THE BH: HEATING (WITHOUT DHW)
TYPE OF FUEL: FIREWOOD, PEAT, WOOD BRIQUETTES, COAL
FUEL SUPPLY: MANUAL
EFFICIENCY: NOT LESS THAN 85%
TEMPERATURE GRAPH: 95° C / 70° C (MAX); 80° C / 60° C (ACCEPTABLE)
OPERATING PRESSURE OF COOLANT, MPA: 6.0
CONNECTION SCHEME: DEPENDED
SUPPLY VOLTAGE OF ELECTRICAL EQUIPMENT, V: ~380/~220
TECHNOLOGICAL PROTECTION: REQUIRED
EMERGENCY PROTECTION: REQUIRED
ACTUATION TIME OF PROTECTIVE DEVICES, NO MORE, S: 60
SIGNALING: AUTOMATICALLY
FLUE GAS CLEANING: NOT REQUIRED
METERS: THERMAL ENERGY, WATER, MAKE-UP WATER, ELECTRICITY
GROUNDING: INTERNAL GROUND LOOP
THE DESIGN OF THE CONTAINER: NO SPECIAL REQUIREMENTS
HEIGHT OF CONTAINER ON THE TRAWL: NO MORE, THAN 3.95 M
WIDTH OF THE CONTAINER OR ITS SEPARABLE PARTS: NO MORE, THAN 2.6 M
CONTAINER INSULATION: REQUIRED
AVERAGE SERVICE LIFE, NOT LESS THAN, YEARS: 15
CONNECT MBH€„¢S PROTECTION AND SAFETY SYSTEMS TO AN UNINTERRUPTED POWER SUPPLY SOURCE.
MOBILE BOILER HOUSES WILL BE CONNECTED TO HEAT SUPPLY NETWORKS (STATIC PRESSURE €€Œ UP TO 25 METERS OF WATER COLUMN) AND WATER SUPPLY (PRESSURE €€Œ FROM 0.5 ATM TO 3.0 ATM) USING FLEXIBLE HOSES OF THE APPROPRIATE PARAMETERS ( FLEXIBLE HOSES 10 METERS LONG EACH AND VALVES ARE INCLUDED IN THE DELIVERY).
THE MODULE MUST CONTAIN A PROPRIETARY PLATE MARKING PASSPORT DATA AFFIXED IN A PERCUSSION OR OTHER EQUIVALENT WAY, ENSURING THE CLARITY AND DURABILITY OF THE IMAGE, WHICH CONTAINS THE FOLLOWING INFORMATION:
A) NAME, TRADEMARK OF THE MANUFACTURER;
B) DESIGNATION OF THE MODULE;
C) NUMBER ACCORDING TO THE NUMBERING SYSTEM OF THE MANUFACTURER;
D) YEAR OF MANUFACTURE;
E) INSTALLED CAPACITY, MW;
F) WORKING PRESSURE, MPA;
G) NOMINAL TEMPERATURE, º�¡;
J) DESIGNATION OF TECHNICAL CONDITIONS;
K) CLIMATIC PERFORMANCE.
THE BODY SHOULD BE MARKED WITH A SLINGING SCHEME, CENTER OF GRAVITY AND MASS.
ALL EQUIPMENT, THAT IS PART OF THE MBH MUST ALSO HAVE NAMEPLATES, WHICH SHOULD CONTAIN THE NAME OF THE MANUFACTURER, SERIAL NUMBER, MAIN TECHNICAL CHARACTERISTICS, YEAR OF MANUFACTURE, ETC.
2. THE COMPOSITION OF THE MOBILE BOILER HOUSES INCLUDES:
- SOLID FUEL WATER HEATING BOILER
- THRUST REGULATOR THERMOMECHANICAL
- BOILER SAFETY GROUP
- BOILER RECIRCULATION PUMP, OR A SOLUTION, THAT REPLACES IT
- MAIN PUMPS WITH A FREQUENCY CONVERTER
- FEED PUMPS
- SEDIMENT FILTER
- MEMBRANE EXPANSION TANK, UN
- PURIFIED WATER SUPPLY TANK WITH FLOAT VALVE, SET
- INSTALLATION OF WATER SOFTENING, SET
- COLD WATER METER, SET
- HEAT METER, SET
- BOILER HOUSE CONTROL CABINET, SET
- INPUT ELECTRICAL CABINET, SET
- THE POWER SUPPLY SYSTEM OF THE BOILER HOUSE, SET
- EXTERNAL AND INTERNAL LIGHTING SYSTEM, SET
- SUPPLY AND EXHAUST VENTILATION SYSTEM, SET
- PIPELINES AND FITTINGS OF THE INTERNAL THERMAL CIRCUIT, SET
- PIPELINES AND FITTINGS OF INTERNAL WATER SUPPLY, SET
- DRAINAGE PIPELINES, SET
- GAS DUCTS WITHIN AND OUTSIDE (MIN) THE BOILER HOUSE, SET
- CONTROL AND MEASURING EQUIPMENT AND AUTOMATION, SET
- ELECTRIC CONVECTOR, UN
- DIESEL-ELECTRIC GENERATOR FOR OWN NEEDS, SET
- FIRE CABINET AND POWDER FIRE EXTINGUISHER OP-9
- 2 ELECTRICAL INPUTS (ONE - FROM THE ELECTRICAL NETWORK,
THE SECOND (BACKUP) FROM THE DIESEL GENERATOR).
3 TECHNICAL DOCUMENTS TO BE PROVIDED WITH MBH:
- PASPORT MBH;
- OPERATING INSTRUCTION;
- FACTORY TEST REPORTS;
- PASSPORTS AND OPERATING INSTRUCTIONS FOR EQUIPMENT INCLUDED IN THE MBH;
- WARRANTY CARDS FOR EQUIPMENT€„¢S;
- DRAWING: DIAGRAMS, SPECIFICATIONS, PLANS, SECTIONS
ALL EQUIPMENT SHALL BE OF INDUSTRIAL GRADE AND OF STANDARD CONSTRUCTION, STURDY DESIGN AND MANUFACTURED NO EARLIER THAN 2022. WARRANTY €€Œ AT LEAST 2 YEARS.
THE PRESENCE OF SERVICE CENTERS IN UKRAINE, INCLUDING FOR MAIN 154-UCEM-1810-1201641 Parent award context Parent award agency: Agency for International Development · Agency for International Development Parent award NAICS: 541990 Parent award description: OVERSEAS CONTRACT View parent award on USAspending | — | $3,329,103 | Sep 5, 2023 | — – — |
| Subcontractor | Agency for International Development | BOILERHOUSES FOR ESP BENEFICIARIES 154-UCEM-1810-1194905 Parent award context Parent award agency: Agency for International Development · Agency for International Development Parent award NAICS: 541990 Parent award description: OVERSEAS CONTRACT View parent award on USAspending | — | $1,963,092 | Dec 20, 2022 | — – — |
Contract vehicles are shown only when present in the source record. Linked award numbers and vehicles open the authoritative record on USAspending.gov.
Government-sourced data comes from SAM.gov, SBA and USAspending.gov and is attributed to its source. Items marked company-reported were provided by the company and are verified by FedSub only where labeled. FedSub is a private company and is not affiliated with SBA, GSA/SAM.gov, or any government agency.